Data Line Surge Protector
LPS DL-2/7.5

Specification
Features:
-
Ideal for RS485, RS 422, RS 423,
Ethernet signal of instrumentation interfaces and equipment
such as servers, card reader controllers, lift controllers,
twisted pair CCTV circuit, etc
-
Protects sensitive data networks
against lightning induced surges without impairing the
system normal operation or cause excessive in-line
resistance
-
DL series employs multistage
protection with GDT for primary protection then linked by a
second stage series impedance and semiconductor voltage
dependant device to provide unsurpassed performance in
lightning surge protection
Specification:
|
Technical Specification |
DL-2/7.5 |
| Signal Type |
RS 422, RS 423, RS485, LAN |
| Nominal Operating
Signal Voltage |
±5V |
| Max. Operating Signal Voltage |
±7V |
| Standard Clamp Voltage @ 1mA |
9V (Line-Screen, Line-Line)
90V (Screen - Ground) |
| Left-through Voltage (Line -
Ground) @ IEEE C 62.36 - 1994 (CCITT) / ITU-k.20
Enhanced 6kV, 150A, 10/700μs |
12V(Line-Screen, Line-Line)
600V (Screen - Ground) |
| Max. Surge Current per pair @
8/20μs |
20kA |
|
-3db Band width @ 600 ohm circuit |
From DC to 20MHz |
|
@ 110 ohm circuit |
From DC to > 100MHz |
| Insertion Loss @ 600 ohm
circuit |
<0.1db |
| Max. Signal Current
(Line-Line) |
350mA |
| Loop Resistance |
4 ohm |
| Response Time |
<1ns |
| Connector Interface |
Screw Terminal |
| Mounting Interface |
DIN-Rail / Panel Mount |
| Operation & Storage
Temperature |
-40°C to +70°C |
Ordering Info:
|
Protected Wires |
Model Number |
| 2 Wires + Screen |
DL-2/7.5 |
| 4 Wires + Screen |
DL-4/7.5 |
Dimensions:

If there is a cable screen, need to
connect it to S
If no cable screen available, S need to be connected to
Ground
|