Technical Specification |
LF-4/12 |
| Nominal Operating Signal
Voltage |
± 12V |
| Max. Operating Signal
Voltage |
± 18V |
| Standard Clamp Voltage @1mA |
22V |
| Left-through Voltage
(Line-Ground)@IEEE C 62.36 - 1994 (CCITT) / ITU-k.20
Enhanced 6kV, 150A, 10/700μs |
30V |
| Max. Surge Current per wire @
8/20 μs |
10kA |
| -3db Band width @ 600 ohm
circuit |
DC to 40kHz |
| Insertion Loss @600 |
<0.5db |
| Response time |
<5ns |
| Max. Signal Current |
350mA |
| Connector Interface |
Pluggable Screw Terminal |
| Mounting Interface |
Din Railing / Panel Mount |
| Operation & Storage
Temperature |
-40 to + 70°C |